Detailed explanation:
• Compact size and lightweight.
• High reliability and low price.
• Wide input voltage range.
• High conversion efficiency and low operating temperature rise.
• Built-in filter circuit, minimizing external radiated interference.
• Basic protection circuitry, providing good environmental adaptability.
• 4-hour, 100% full load aging and full-series functional testing.
|
Features |
SAMM-150-1B |
|
|
Rated Output Voltage |
DC +24V |
BAT +27.6V |
|
Output Interface Location |
The eight-pin P=9.5mm covered terminal blocks are labeled AC-L, AC-N, DC+, DC-; BAT-, BAT+, BATSW. |
|
|
Output Voltage Range |
Setting error:±0.5V |
Setting error:±0.6V; |
|
Rated Output Current |
6A |
0.5A |
|
Load current range |
0.5~6A ( MAX=10A ) |
0.2~0.5A ( MAX=0.5A ) |
|
Output Voltage Ripple |
Vp-pmax<180 mV |
Vp-pmax<200 mV |
|
Li;Lo Regulation |
Line:±0.5%;Load:±0.5% |
Line:±1%;Load:±15%(BAT±3%) |
|
Overall Voltage Regulation Accuracy |
±1% |
±16%(BAT±4%) |
|
Rated Output Power |
150W |
|
|
Rated Operating Efficiency |
≥80%(Output power is rated) |
|
|
Rated Input Voltage |
Operating voltage: AC176V-264V; Rated voltage: AC220V; Interface position: Three-position covered socket, labeled AC-L, AC-N, FG. |
|
|
Rated Input Current |
Rated current: AC 0.5A, current range AC 0.5~1A |
|
|
AC Input Frequency |
Rated AC voltage frequency range 47~63Hz, sine wave |
|
|
Inrush Current |
The inrush current to the power grid at the moment of power-on: the maximum value during cold start is 60A/10ms. |
|
|
Output Overload Protection |
The +12V overload protection point is approximately 105%~120% of the rated output power; the overload protection is an online current-limiting and voltage-reducing method; short-circuit protection requires input reset. |
|
|
UPS battery management function |
An external battery (5~30AH capacity) is required as backup power. When AC power fails, the system automatically switches to backup power with a switching time of ≤50ms. When AC power is normal, it automatically switches back to AC power and manages the battery (to enable the UPS function, BAT+ and BAT.SW need to be shorted). |
|
|
It has the function of float charging external batteries (5~30AH), and the battery has undervoltage protection of 10V±0.6V and short circuit protection function with automatic reset when discharging to load. |
||
|
Power supply timing parameters |
Setup time ≈ 200ms; Settlement time ≈ 50ms; Hold-up time ≈ 20ms |
|
|
Dielectric strength parameters |
Input-output: >AC1.5KV; Input-casing: >AC1.5KV; Output-casing: >AC0.5KV; Leakage current <5mA; 50Hz; 1min. |
|
|
Operating temperature parameters |
The operating temperature drift coefficient is approximately ±0.03 [%/℃]; the absolute temperature rise coefficient is approximately 0.50 [℃/W]; the absolute temperature rise of the chassis when operating at rated power is 25℃±5℃. |
|
|
Environmental conditions parameters |
Storage environment: -20℃ to +85℃; 10% to 95%RH. Operating environment: -10℃ to +50℃; 20% to 90%RH. (Varies depending on the operating environment and power consumption) |
|
|
Cooling method |
Designed for continuous operation, with self-cooling and heat dissipation assistance. (Power consumption and lifespan are affected by differences in the usage environment and installation location.) |
|
|
External dimensions and mounting dimensions |
Specifications: L195×W110×H50mm³; Installation dimensions: L188×W98mm², L188×W23mm² |
|
|
Net weight and color |
The total weight is approximately 850g; the bottom shell is made of 1.5mm thick aluminum with a sandblasted silver finish; the top shell is made of 0.8mm thick iron with an electroplated silver finish. |
|
|
Certification Security Specifications |
National Standard GB-4943 |
|
Note: 1) All the above test indicators were measured under the following conditions: within the rated input voltage and rated output load range, the environment was 25℃, 85%RH, and there was no wind.
2) Output DC voltage ripple test: A parallel stranded wire with a length of 30cm and a cross-section of 1mm², with 0.1μF and 0.47μF capacitors connected to one end, was bypassed at the test point. The maximum peak-to-peak value of the main frequency ripple Vp-p100Hz and the maximum peak-to-peak value of the combined ripple Vp-pmax were measured respectively.
3) Li voltage regulation rate: When the load is at the rated value, the input voltage varies within the rated range; Lo load regulation rate: When the input is at the rated voltage value, the load varies from zero to the rated value.
Welcome to our company, a professional R&D enterprise specializing in switching power supplies, security access control power supplies, and other related products.