Welcome to Shenzhen Shansheng Hongqi Technology Co., Ltd.!
Detailed explanation:
|
• Compact size and lightweight. • High reliability and low price. • Wide input voltage range. • High conversion efficiency and low operating temperature rise. • Built-in filter circuit, minimizing external radiated interference. • Basic protection circuitry, providing good environmental adaptability. • 4-hour, 100% full load aging and full-series functional testing. |
||
|
Features |
SAOG-250-1B |
|
|
Rated Output Voltage |
DC +24V |
BAT +27.6V |
|
Output Interface Location |
The four terminals are labeled DC+, DC-, BAT-, BAT+, and BAT.SW. |
|
|
Output Voltage Range |
Setting error: ±0.2V; Adjustable range: ±10% |
Setting error: ±0.5V; |
|
Rated Output Current |
10A |
1A |
|
Load current range |
0~10A ( MAX=10A ) |
0~1A ( MAX=1A ) |
|
Output Voltage Ripple |
Vnor<9mV ;Vp-p100Hz<200mV;Vp-pmax<200 mV |
Vnor<12mV ;Vp-p100Hz<220mV;Vp-pmax<250 mV |
|
Li;Lo Regulation |
Line:±0.5%;Load:±0.8% |
Line:±1%;Load:±15 % |
|
Overall Voltage Regulation Accuracy |
±1% |
±20% |
|
Rated Output Power |
250W |
|
|
Rated Operating Efficiency |
≥75% (output power is rated value) |
|
|
Rated Input Voltage |
Rated voltage: AC176~265V, operating voltage: AC220V±15%. Interface position: Three-position open socket, labeled AC-L, AC-N, FG. |
|
|
Rated Input Current |
Rated current: AC 3.0A, current range AC 1.0~4.0A |
|
|
AC Input Frequency |
Rated AC voltage frequency range 47~63Hz, sine wave |
|
|
Inrush Current |
The inrush current to the power grid at the moment of power-on: the maximum value during cold start is 60A/10ms. |
|
|
Input Overvoltage Protection |
Input allowable range: AC0~280V; Overvoltage protection point: AC300V±5V, power supply enters irreversible shutdown state. |
|
|
Output Overload Protection |
The +24V overload protection point is approximately 105%~120% of the rated output power; the overload protection is an online current-limiting and voltage-reducing method; short-circuit protection requires input reset. |
|
|
UPS battery management function |
An external 24V lead-acid battery (5~30AH capacity) is required as backup power. The system automatically switches to backup power when AC power is interrupted, and the system switching is uninterrupted. When AC power is normal, it automatically switches back to AC power and manages the battery. |
|
|
It has a float charging function for external batteries (5~30AH), and all protection functions can be automatically reset. |
||
|
Power supply timing parameters |
Setup time ≈ 200ms; Settlement time ≈ 50ms; Hold-up time ≈ 20ms |
|
|
Dielectric strength parameters |
Input-output: AC1.5KV; Input-casing: AC1.5KV; Output-casing: AC0.5KV; Leakage current 5mA; 50Hz; 1min. |
|
|
Operating temperature parameters |
The operating temperature drift coefficient is approximately ±0.03 [%/℃]; the absolute temperature rise coefficient is approximately 0.50 [℃/W]; the absolute temperature rise of the chassis when operating at rated power is 35℃±5℃. |
|
|
Environmental conditions parameters |
Storage environment: -20℃ to +85℃; 10% to 95%RH. Operating environment: 0℃ to +45℃; 20% to 90%RH. (Varies depending on usage environment and power consumption) |
|
|
Cooling method |
Designed for continuous operation, air-cooled (power consumption and lifespan are affected by the operating environment and installation location). |
|
|
External dimensions and mounting dimensions |
Specifications and dimensions: L225×W118×H69mm3; |
|
|
Net weight and color |
The total weight is approximately 1.0 kg; the shell is a 1.0 mm thick iron shell with a white surface. |
|
|
Certification Security Specifications |
National Standard GB-4943 |
|
|
Note: 1) All the above test indicators were measured under the following conditions: within the rated input voltage and rated output load range, the environment was 25℃, 85%RH, and there was no wind. 2) Output DC voltage ripple test: A parallel stranded wire with a length of 30cm and a cross-section of 1mm², with 0.1μF and 0.47μF capacitors connected to one end, was bypassed at the test point. The maximum peak-to-peak value of the main frequency ripple Vp-p100Hz and the maximum peak-to-peak value of the combined ripple Vp-pmax were measured respectively. 3) Li voltage regulation rate: When the load is at the rated value, the input voltage varies within the rated range; Lo load regulation rate: When the input is at the rated voltage value, the load varies from zero to the rated value. |
||